Bibliographic information
GuidelineInfection prevention and control in the context of coronavirus disease (COVID-19): a living guideline, 9 October 2023.
Year of Publication2023
Issuing InstitutionWHO
Recommendation
Maintained
Originally developed
The WHO recommends adhering to the ventilation rate requirements for health-care facilities in the context of COVID-19:
- 160 l/s/patient for airborne precaution rooms
- 60 l/s/patient for general wards and outpatient departments
Recommended in favor
Strong
Certainty of evidence
Very low
Notes and Remarks
Implementation considerations
- The airflow direction should be from clean to less clean areas.
- Air should be exhausted directly to the outside away from air-intake vents, people and animals.
- Heating, Ventilation and Air Conditioning (HVAC) systems should be operated continuously when people are in the building and should be regularly inspected, maintained and cleaned.
- AGPs should be performed in rooms equipped with negative-pressure ventilation systems, in keeping with airborne precautions.
- If no other strategy can be adopted to meet the ventilation rate minimum requirements, consider using a stand-alone air cleaner equipped with High-Efficiency Particulate Air (HEPA) filters.
- For additional information on implementing ventilation standards and strategies to improve a health-care facility's ventilation, see Roadmap to improve and ensure good indoor ventilation in the context of COVID-19 [9].
Also Featured In
This recommendation also appears in the following guidelines:
Guideline
Infection prevention and control in the context of coronavirus disease (COVID-19): A guideline
Year2023
InstitutionWHO