The WHO recommends adhering to the ventilation rate requirements for health-care facilities in the context of COVID-19:

  • 160 l/s/patient for airborne precaution rooms
  • 60 l/s/patient for general wards and outpatient departments

Recommended in favor

Strong

Notes and Remarks

Implementation considerations

  • The airflow direction should be from clean to less clean areas.
  • Air should be exhausted directly to the outside away from air-intake vents, people and animals.
  • Heating, Ventilation and Air Conditioning (HVAC) systems should be operated continuously when people are in the building and should be regularly inspected, maintained and cleaned.
  • AGPs should be performed in rooms equipped with negative-pressure ventilation systems, in keeping with airborne precautions.
  • If no other strategy can be adopted to meet the ventilation rate minimum requirements, consider using a stand-alone air cleaner equipped with High-Efficiency Particulate Air (HEPA) filters.
  • For additional information on implementing ventilation standards and strategies to improve a health-care facility's ventilation, see Roadmap to improve and ensure good indoor ventilation in the context of COVID-19 [9].